Rockwell Automation Publication 1756-UM020I-EN-P - August 2012

143

Appendix

B

Maintain the Battery

GuardLogix 1756-L6

xS primary controllers and 1756-LSP safety partners

contain a lithium battery which may need to be replaced. GuardLogix 1756-L7

xS

controllers and 1756-L7SP safety partners do not have a battery.

Estimate Battery Life

Battery life is dependent upon chassis temperature, project size, and how often
you cycle power to the controller. Battery life is not dependent upon whether or
not the controller has power.

Before BAT Indicator Turns On

Use this table to estimate the worst case time before the BAT indicator turns red.

Topic

Page

Estimate Battery Life

143

When to Replace the Battery

145

Replace the Battery

145

Store Replacement Batteries

147

Table 52 - Battery Indicator Estimate (worst-case)

Temperature 2.54 cm

(1 in.) Below Chassis

Power Cycles per

Day

Project Size

1 MB

2 MB

4 MB

8 MB

0…40 °C (32…104 °F)

3

3 years

3 years

26 months

20 months

2 or less

3 years

3 years

3 years

31 months

41…45 °C (105…113 °F)

3

2 years

2 years

2 years

20 months

2 or less

2 years

2 years

2 years

2 years

46…50 °C (114…122 °F)

3 or less

16 months

16 months

16 months

16 months

51…55 °C (123…131 °F)

3 or less

11 months

11 months

11 months

11 months

56…60 °C (132…140 °F)

3 or less

8 months

8 months

8 months

8 months

EXAMPLE

Under the following conditions, the battery will last at least 20 months
before the BAT indicator turns red:

Maximum temperature 2.54 cm (1 in.) below the chassis is 45 °C

(113 °F).

Power is cycled three times per day.
The controller contains a 8 MB project.