B - maintain the battery, Estimate battery life, Before bat indicator turns on – Rockwell Automation 1756-SPESMNRMXT GuardLogix Controllers User Manual Manuel d'utilisation
Page 143: Appendix b, Maintain the battery, Appendix
Rockwell Automation Publication 1756-UM020I-EN-P - August 2012
143
Appendix
B
Maintain the Battery
GuardLogix 1756-L6
xS primary controllers and 1756-LSP safety partners
contain a lithium battery which may need to be replaced. GuardLogix 1756-L7
xS
controllers and 1756-L7SP safety partners do not have a battery.
Estimate Battery Life
Battery life is dependent upon chassis temperature, project size, and how often
you cycle power to the controller. Battery life is not dependent upon whether or
not the controller has power.
Before BAT Indicator Turns On
Use this table to estimate the worst case time before the BAT indicator turns red.
Topic
Page
Table 52 - Battery Indicator Estimate (worst-case)
Temperature 2.54 cm
(1 in.) Below Chassis
Power Cycles per
Day
Project Size
1 MB
2 MB
4 MB
8 MB
0…40 °C (32…104 °F)
3
3 years
3 years
26 months
20 months
2 or less
3 years
3 years
3 years
31 months
41…45 °C (105…113 °F)
3
2 years
2 years
2 years
20 months
2 or less
2 years
2 years
2 years
2 years
46…50 °C (114…122 °F)
3 or less
16 months
16 months
16 months
16 months
51…55 °C (123…131 °F)
3 or less
11 months
11 months
11 months
11 months
56…60 °C (132…140 °F)
3 or less
8 months
8 months
8 months
8 months
EXAMPLE
Under the following conditions, the battery will last at least 20 months
before the BAT indicator turns red:
• Maximum temperature 2.54 cm (1 in.) below the chassis is 45 °C
(113 °F).
• Power is cycled three times per day.
• The controller contains a 8 MB project.