Install the Controller
Chapter 2
To connect a workstation to the serial port, use one of these cables:
• 1756-CP3 serial cable
• 1747-CP3 cable from the SLC
product family (If you use this cable,
the controller door may not close.)
If you make your own serial cable,
follow these guidelines.
• Limit the length to 15.2 m
(50 ft).
• Wire the connectors as shown.
• Attach the shield to both
connectors.
Follow these steps to use RSLinx software to configure the RS-232 DF1 device
driver for serial communication.
1. In RSLinx software, from the Communications menu, choose Configure
Drivers.
Controller End
Workstation End
2 RDX
3 TXD
4 DTR
COMMON
6 DSR
7 RTS
8 CTS
9
1 CD
2 RDX
3 TXD
4 DTR
COMMON
6 DSR
7 RTS
8 CTS
9
1 CD
Workstation
Controller
- 1756-SPESMNRM GuardLogix Controllers User Manual 1756-SPESMNSEXT GuardLogix Controllers User Manual 1756-SPESMNSE GuardLogix Controllers User Manual 1756-ESMNRMXT GuardLogix Controllers User Manual 1756-ESMNRM GuardLogix Controllers User Manual 1756-ESMNSEXT GuardLogix Controllers User Manual 1756-ESMNSE GuardLogix Controllers User Manual 1756-ESMCAPXT GuardLogix Controllers User Manual 1756-ESMCAP GuardLogix Controllers User Manual 1756-L7x GuardLogix Controllers User Manual 1756-LSP GuardLogix Controllers User Manual 1756-L6x GuardLogix Controllers User Manual