A - status indicators, 1756-l6xs controller status indicators, Appendix a – Rockwell Automation 1756-SPESMNRMXT GuardLogix Controllers User Manual Manuel d'utilisation
Page 135: Status indicators, 1756-l6, Appendix

Rockwell Automation Publication 1756-UM020I-EN-P - August 2012
135
Appendix
A
Status Indicators
1756-L6xS Controller Status
Indicators
Primary controller and safety partner status is displayed by LED status indicators.
Topic
Page
1756-L6xS Controller Status Indicators
1756-L7xS Controllers Status Indicators
1756-L7xS Controller Status Display
Table 44 - 1756-L6xS Status Indicator Descriptions
Indicator
Status
Primary Controller Description
Safety Partner Description
RUN
Off
No user tasks running. Controller is in PROGram mode.
N/A
Green
Controller is in RUN mode.
N/A
SAFE RUN
Off
N/A
The user safety task or safety outputs are disabled. The controller
is in the PROGram mode, Test mode, or the safety task is faulted.
Green
N/A
The user safety task and safety outputs are enabled. The safety
application is executing. Safety task signature is present.
Green, Flashing
N/A
The user safety task and safety outputs are enabled. The safety
application is executing. Safety task signature is not present.
FORCE
Off
No forces, standard or safety, are enabled on the controller.
N/A
Amber
Standard and/or safety forces have been enabled.
N/A
Amber, Flashing
One or more I/O addresses, standard and/or safety, have been
forced to an on or off state, but forces are not enabled.
N/A
BAT
Off
The battery is able to support memory.
The battery is able to support memory.
Red
The battery is not able to support memory.
The battery is not able to support memory.
OK
Off
No power is applied.
No power is applied.
Green
The controller is operating with no faults.
The safety partner is operating with no faults.
Red, Flashing
Nonrecoverable fault or recoverable fault not handled in the fault
handler. All user tasks, both standard and safety, are stopped.
N/A
Red
Powering up or nonrecoverable controller fault.
Powering up or nonrecoverable controller fault.
I/O
(1)
Off
No activity. No I/O is configured.
N/A
Green
The controller is communicating to all configured I/O devices, both
standard and safety.
N/A
Green, Flashing
One or more I/O devices is not responding.
N/A
Red, Flashing
Controller is not communicating to configured I/O.
N/A
- 1756-SPESMNRM GuardLogix Controllers User Manual 1756-SPESMNSEXT GuardLogix Controllers User Manual 1756-SPESMNSE GuardLogix Controllers User Manual 1756-ESMNRMXT GuardLogix Controllers User Manual 1756-ESMNRM GuardLogix Controllers User Manual 1756-ESMNSEXT GuardLogix Controllers User Manual 1756-ESMNSE GuardLogix Controllers User Manual 1756-ESMCAPXT GuardLogix Controllers User Manual 1756-ESMCAP GuardLogix Controllers User Manual 1756-L7x GuardLogix Controllers User Manual 1756-LSP GuardLogix Controllers User Manual 1756-L6x GuardLogix Controllers User Manual