Chapter 6
Develop Safety Applications
5. Click Advanced if you want to change the type of connection by
unchecking ‘Allow Unicast Consumer Connections’.
6. Click OK.
Consume Safety Tag Data
Follow these steps to consume data produced by another controller.
1. In the consumer controller’s project, create a user-defined data type
identical to the one created in the producer project.
2. Right-click Controller Tags and choose New Tag.
3. Set the Type as Consumed, the Class as Safety, and the Data Type to the
user-defined data type you created in step
1
.
TIP
The user-defined type can be copied from the producer project
and pasted into the consumer project.
Advertising
Ce manuel est liée aux produits suivants:
- 1756-SPESMNRM GuardLogix Controllers User Manual 1756-SPESMNSEXT GuardLogix Controllers User Manual 1756-SPESMNSE GuardLogix Controllers User Manual 1756-ESMNRMXT GuardLogix Controllers User Manual 1756-ESMNRM GuardLogix Controllers User Manual 1756-ESMNSEXT GuardLogix Controllers User Manual 1756-ESMNSE GuardLogix Controllers User Manual 1756-ESMCAPXT GuardLogix Controllers User Manual 1756-ESMCAP GuardLogix Controllers User Manual 1756-L7x GuardLogix Controllers User Manual 1756-LSP GuardLogix Controllers User Manual 1756-L6x GuardLogix Controllers User Manual