Safety tag mapping – Rockwell Automation 1756-SPESMNRMXT GuardLogix Controllers User Manual Manuel d'utilisation

Page 102

Advertising
background image

102

Rockwell Automation Publication 1756-UM020I-EN-P - August 2012

Chapter 6

Develop Safety Applications

9. If the Connection Reaction time limit is acceptable, click OK; or for more

complex requirements, click Advanced to set the Advanced Connection
Reaction Time Limit parameters.

The Timeout Multiplier determines the number of RPIs to wait for a
packet before declaring a connection timeout.

The Network Delay Multiplier defines the message transport time that is
enforced by the CIP Safety protocol. The Network Delay Multiplier
specifies the round-trip delay from the producer to the consumer and back
to the producer. You can use the Network Delay Multiplier to increase or
decrease the Connection Reaction Time Limit.

Safety Tag Mapping

Controller-scoped standard tags cannot be directly accessed by a safety routine.
To allow standard tag data to be used within safety task routines, the GuardLogix
controllers provide a safety tag mapping feature that lets standard tag values be
copied into safety task memory.

Table 31 - Additional Resources

Resource

Description

Pages

71

75

Provides more information on setting the RPI and understanding
how the Max. Network Delay, Timeout Multiplier, and Network
Delay Multipliers affect the Connection Reaction Time

Chapter 9

Contains information on the CONNECTION_STATUS predefined
data type

Logix5000 Controllers Produced and Consumed
Tags Programming Manual, publication

1756-

PM011

Provides detailed information on using produced and consumed
tags

Advertising