Monitoring safety status, Controller faults, Monitoring safety status controller faults – Rockwell Automation 1756-SPESMNRMXT GuardLogix Controllers User Manual Manuel d'utilisation
Page 128

128
Rockwell Automation Publication 1756-UM020I-EN-P - August 2012
Chapter 9
Monitor Status and Handle Faults
Monitoring Safety Status
View controller safety status information on the safety status button on the
online bar and on the Safety tab of the Controller Properties dialog box.
Figure 33 - Safety Task Status
These are the possible values for safety status:
• Safety partner is missing or unavailable.
• Safety partner hardware is incompatible with primary controller.
• Safety partner firmware is incompatible with the primary controller.
• Safety task inoperable.
• Safety task OK.
With the exception of safety task OK, the descriptions indicate that
nonrecoverable safety faults exist.
See
Major Safety Faults (Type 14) on page 130
for fault codes and corrective
actions.
The status of the safety partner can be viewed on the Connections tab of its
Module Properties dialog box.
Figure 34 - Safety Partner Status
Controller Faults
Faults in the GuardLogix system can be nonrecoverable controller faults,
nonrecoverable safety faults in the safety application, or recoverable safety faults
in the safety application.
- 1756-SPESMNRM GuardLogix Controllers User Manual 1756-SPESMNSEXT GuardLogix Controllers User Manual 1756-SPESMNSE GuardLogix Controllers User Manual 1756-ESMNRMXT GuardLogix Controllers User Manual 1756-ESMNRM GuardLogix Controllers User Manual 1756-ESMNSEXT GuardLogix Controllers User Manual 1756-ESMNSE GuardLogix Controllers User Manual 1756-ESMCAPXT GuardLogix Controllers User Manual 1756-ESMCAP GuardLogix Controllers User Manual 1756-L7x GuardLogix Controllers User Manual 1756-LSP GuardLogix Controllers User Manual 1756-L6x GuardLogix Controllers User Manual