Rockwell Automation Publication 1756-UM020I-EN-P - August 2012

125

Chapter

9

Monitor Status and Handle Faults

See

Appendix A

,

Status Indicators

for information on interpreting the

controller’s status indicators and display messages.

Viewing Status via the Online
Bar

The online bar displays project and controller information, including the
controller’s status, force status, online edit status, and safety status.

Figure 31 - Status Buttons

When the Controller Status button is selected as shown above, the online bar
shows the controller’s mode (RUN) and status (OK). The BAT indicator
combines the status of the primary controller and the safety partner. If either or
both have a battery fault, the status indicator illuminates. The I/O indicator
combines the status of standard and Safety I/O and behaves just like the status
indicator on the controller. The I/O with the most significant error status is
displayed next to the status indicator.

When the Safety Status button is selected as shown below, the online bar displays
the safety task signature.

Figure 32 - Safety Signature Online Display

Topic

Page

Viewing Status via the Online Bar

125

Monitoring Connections

126

Monitoring Safety Status

128

Controller Faults

128

Developing a Fault Routine

131

Controller Status Button

Force Status Button

Online Edit Button

Safety Status Button