Chapter 5

Add, Configure, Monitor, and Replace CIP Safety I/O

Table 22 - Status Indicator Operation

Indicator

Status

Description

Guard I/O DeviceNet Modules

Guard I/O EtherNet/IP Modules

POINT Guard I/O Modules

Module
Status (MS)

Off

No power.

Green, On

Operating under normal conditions.

Green, Flashing

Device is idle.

Red, Flashing

A recoverable fault exists.

A recoverable fault exists or a firmware update is in progress.

Red, On

An unrecoverable fault exists.

Red/Green,
Flashing

Self-tests in progress.

Self-tests are in progress or the module is not configured properly. See the network status
indicator for more information.

Network
Status (NS)

Off

Device is not online or may not have power.

Green, On

Device is online; connections are established.

Green, Flashing

Device is online; no connections established.

Red, Flashing

Communication timeout.

Communication timeout or a firmware update is in progress.

Red, On

Communication failure. The device has detected an error that has prevented network communication.

Red/Green,
Flashing

Device is in Communication Faulted state or
safety network number (SNN) is being set.

Self-test in progress.

Not applicable.

Input Points
(INx)

Off

Safety input is OFF.

Yellow, On

Safety input is ON.

Red, On

An error has occurred in the input circuit.

Red, Flashing

When dual-channel operation is selected, an error has occurred in the partner input circuit.

Output Points
(Ox)

Off

Safety output is OFF.

Yellow, On

Safety output is ON.

Red, On

An error has occurred in the output circuit.

Red, Flashing

When dual-channel operation is selected, an error has occurred in the partner output circuit.

Test Output
Points (Tx)

Off

Not applicable.

The output is OFF.

Not applicable.

Yellow, On

The output is ON.

Red. On

An error has occurred in the output circuit.

LOCK

Yellow, On

Device configuration is locked.

RSLogix 5000 software does not support this function.

Yellow, Flashing

Device configuration is valid, but device is not
locked.

Yellow, Off

Invalid, no configuration data, or device has
been configured by RSLogix 5000 software.

IN PWR

Green, Off

No input power.

Not applicable.

Green, On

Input power voltage is within specification.

Yellow, On

Input power voltage is out of specification.

OUT PWR

Green, Off

No output power.

Green, On

Output power voltage is within specification.

Yellow, On

Output power voltage is out of specification.

PWR

Green, Off

Not applicable.

No power.

Green, On

Power voltage is within specification.

Yellow, On

Power voltage is out of specification.