Update the controller, Using controlflash software to update firmware – Rockwell Automation 1756-SPESMNRMXT GuardLogix Controllers User Manual Manuel d'utilisation
Page 39

Rockwell Automation Publication 1756-UM020I-EN-P - August 2012
39
Install the Controller
Chapter 2
c. Click Auto-Configure.
6. If the auto configuration is successful, click OK.
If the auto configuration is not successful, verify that the correct Comm
Port was selected.
7. Click Close.
Update the Controller
The controllers ship without firmware. Controller firmware is packaged with
RSLogix 5000 programming software. In addition, controller firmware is also
available for download from the Rockwell Automation Technical Support
website at
You can upgrade your firmware by using either ControlFLASH™ software, which
is packaged with RSLogix 5000 software or by using the AutoFlash feature of
RSLogix 5000 software.
Using ControlFLASH Software to Update Firmware
With ControlFLASH software, version 8 or later (RSLogix 5000 software,
version 18 or later) software, the safety partner updates automatically, when the
primary controller is updated.
IMPORTANT
On 1756-L7xS controllers, if the SD card is locked and the stored project’s Load
Image option is set to On Power Up, the controller firmware is not updated as a
result of these steps. Any previously-stored firmware and projects are loaded
instead.
- 1756-SPESMNRM GuardLogix Controllers User Manual 1756-SPESMNSEXT GuardLogix Controllers User Manual 1756-SPESMNSE GuardLogix Controllers User Manual 1756-ESMNRMXT GuardLogix Controllers User Manual 1756-ESMNRM GuardLogix Controllers User Manual 1756-ESMNSEXT GuardLogix Controllers User Manual 1756-ESMNSE GuardLogix Controllers User Manual 1756-ESMCAPXT GuardLogix Controllers User Manual 1756-ESMCAP GuardLogix Controllers User Manual 1756-L7x GuardLogix Controllers User Manual 1756-LSP GuardLogix Controllers User Manual 1756-L6x GuardLogix Controllers User Manual