Safety Task Signature and Safety-locked and -unlocked Status

The existence of a safety task signature and the safety-locked or -unlocked status
of the controller affect both the upload and download processes.

On Upload

If the controller has a safety task signature, the safety task signature and the safety
task lock status are uploaded with the project. For example, if the project in the
controller was safety-unlocked, the offline project remains safety-unlocked
following the upload, even if it was locked prior to the upload.

Following an upload, the safety task signature in the offline project matches the
controller’s safety task signature.

On Download

The existence of a safety task signature, and the controller’s safety-lock status,
determines whether or not a download can proceed.

Table 34 - Effect of Safety-lock and Safety Task Signature on Download Operation

Safety-lock Status

Safety Task Signature Status

Download Functionality

Controller safety-unlocked

Safety task signature in the offline project
matches the safety task signature in the
controller.

All standard project components are downloaded. Safety tags are reinitialized to the values they
had when the safety task signature was created. The safety task is not downloaded. Safety lock
status matches the status in the offline project.

Safety task signatures do not match.

If the controller had a safety task signature, it is automatically deleted, and the entire project is
downloaded. Safety lock status matches the status in the offline project.

Controller safety-locked

Safety task signatures match.

If the offline project and the controller are safety-locked, all standard project components are
downloaded and the safety task is re initialized to the values they had when the safety task
signature was created.
If the offline project is not safety-locked, but the controller is, the download is blocked and you
must first unlock the controller to allow the download to proceed.

Safety task signatures do not match.

You must first safety-unlock the controller to allow the download to proceed. If the controller had a
safety task signature, it is automatically deleted, and the entire project is downloaded. Safety lock
status matches the status in the offline project.

IMPORTANT

During a download to a controller that is safety-unlocked, if firmware in the
controller is different than in the offline project, do one of the following:

Update the controller so that it matches the offline project. Once the

update is completed, the entire project is downloaded.

Update the project to the controller version.
If you update the project, the safety task signature is deleted, and the
system requires revalidation.