Add, Configure, Monitor, and Replace CIP Safety I/O

Chapter 5

Scenario 1 - Replacement Module is Out-of-box and Safety Signature Exists

1. Remove the old I/O module and install the new module.

2. Right-click the replacement POINT Guard I/O module and choose

Properties.

3. Click

to the right of the safety network number to open the Safety

Network Number dialog box.

4. Click Set.

Yes

No SNN
(Out-of-box)

See Scenario 1 - Replacement Module is Out-of-box and Safety
Signature Exists on page 81

.

Yes

Different SNN from
original safety task
configuration

See Scenario 2 - Replacement Module SNN is Different from Original
and Safety Signature Exists on page 82
.

No

See Scenario 3 - Replacement Module SNN is Different from Original
and No Safety Signature Exists on page 84

.

Table 24 - Replacing a Module

GuardLogix Safety
Signature Exists

Replacement
Module Condition

Action Required