1756-l7xs controller status display, Safety status messages, 1756-l7 – Rockwell Automation 1756-SPESMNRMXT GuardLogix Controllers User Manual Manuel d'utilisation
Page 137

Rockwell Automation Publication 1756-UM020I-EN-P - August 2012
137
Status Indicators
Appendix A
The 1756-L7SP safety partner has an OK status indicator.
1756-L7xS Controller Status
Display
The 1756-L7
xS controller status display scrolls messages that provide
information about the controller’s firmware revision, energy storage module
(ESM) status, project status, and major faults.
Safety Status Messages
The primary controller display may show the following messages. The safety
partner displays ‘L7SP’.
OK
Off
No power is applied.
Green
The controller is operating with no faults.
Red, Flashing
• Nonrecoverable fault or recoverable fault not handled in the fault
handler. All user tasks, both standard and safety, are stopped.
• If the controller is new, out-of-the-box, it requires a firmware
upgrade. The status display indicates Firmware Installation
Required.
Red
• The controller is completing power-up diagnostics
• A nonrecoverable major fault occurred and the program was cleared
from memory.
• The charge of the capacitor in the Energy Storage Module (ESM) is
being discharged upon powerdown.
• The controller is powered but inoperable.
• The controller is loading a project to nonvolatile memory.
Table 46 - 1756-L7SP Status Indicator
Indicator
Status
Description
OK
Off
No power is applied.
Green
The safety partner is operating with no faults.
Red
Powering up or nonrecoverable controller fault.
Table 45 - 1756-L7xS Primary Controller Status Indicator Descriptions
Indicator
Status
Description
Table 47 - Safety Status Display
Message
Interpretation
No Safety Signature
Safety Task is in Run mode without a safety task signature.
Safety Partner Missing
The safety partner is missing or unavailable.
Hardware Incompatible
The safety partner and primary controller hardware is incompatible.
Firmware Incompatible
The safety partner and primary controller firmware revision levels are
incompatible.
No CST Master
A coordinated system time (CST) master has not been found
Safety Task Inoperable
The safety logic is invalid. For example, a mismatch occurred between the primary
controller and the safety partner, a watchdog timeout occurred, or memory is
corrupt.
Safety Unlocked
The controller is in Run mode with a safety signature, but is not safety-locked.
- 1756-SPESMNRM GuardLogix Controllers User Manual 1756-SPESMNSEXT GuardLogix Controllers User Manual 1756-SPESMNSE GuardLogix Controllers User Manual 1756-ESMNRMXT GuardLogix Controllers User Manual 1756-ESMNRM GuardLogix Controllers User Manual 1756-ESMNSEXT GuardLogix Controllers User Manual 1756-ESMNSE GuardLogix Controllers User Manual 1756-ESMCAPXT GuardLogix Controllers User Manual 1756-ESMCAP GuardLogix Controllers User Manual 1756-L7x GuardLogix Controllers User Manual 1756-LSP GuardLogix Controllers User Manual 1756-L6x GuardLogix Controllers User Manual