Chapter 2

Install the Controller

Make Communication
Connections

1756-L7

xS controllers feature a USB port. See

Connect to the 1756-L7xS

Controller’s USB Port

.

1756-L6

xS controllers feature a serial port. See

Connect to the 1756-L6xS

Controller’s Serial Port on page 36

.

Connect to the 1756-L7xS Controller’s USB Port

The controller has a USB port that uses a Type B receptacle. The port is USB 2.0-
compatible and runs at 12 M.

To use the USB port of the controller, you must have RSLinx software, version
2.59 or later, installed on your workstation. Use a USB cable to connect your
workstation to the USB port. With this connection, you can upgrade firmware
and download programs to the controller directly from your workstation.

Figure 3 - USB Connection

ATTENTION: The USB port is intended for temporary local programming
purposes only and not intended for permanent connection.

The USB cable must not exceed 3.0 m (9.84 ft) and must not contain hubs.

WARNING: Do not use the USB port in hazardous locations.