Appendix A
Status Indicators
1756-L7xS Controllers Status
Indicators
The status of the primary controller is displayed via four status indicators.
RS232
Off
There is no activity.
N/A
Green
Data is being received or transmitted.
N/A
SAFETY TASK
Off
N/A
No partnership established. Primary controller is missing, is not
functioning properly, or its firmware revision is incompatible
with that of the safety partner.
Green
N/A
Safety controller status is OK. The coordinated system time (CST)
is synchronized and safety I/O connections are established.
Green, Flashing
N/A
Safety controller status is OK. The coordinated system time (CST)
is not synchronized on the primary controller or the safety
partner.
Red
N/A
Partnership was lost and a new partnership has not been
established. Primary controller is missing, is not functioning
properly, or its firmware revision is incompatible with that of the
safety partner.
Red, Flashing
N/A
Safety task is Inoperable.
(1) I/O includes produced/consumed tags from other controllers.
Table 44 - 1756-L6xS Status Indicator Descriptions
Indicator
Status
Primary Controller Description
Safety Partner Description
Table 45 - 1756-L7xS Primary Controller Status Indicator Descriptions
Indicator
Status
Description
RUN
Off
No user tasks running. Controller is in PROGram mode.
Green
Controller is in RUN mode.
FORCE
Off
No forces, standard or safety, are enabled on the controller.
Amber
Standard and/or safety forces have been enabled.
Use caution if you install (add) a force. If you install a force, it
takes immediate effect.
Amber, Flashing
One or more I/O addresses, standard and/or safety, have been forced to
an on or off state, but forces are not enabled.
Use caution if you enable I/O forces. If you enable I/O forces, all
existing I/O forces also take effect.
SD
Off
No activity is occurring with the memory card.
Green, Flashing
The controller is reading from or writing to the memory card. Do not
remove the memory card while the controller is reading or writing.
Green
Red, Flashing
The memory card does not have a valid file system.
Red
The memory card is not recognized by the controller.
- 1756-SPESMNRM GuardLogix Controllers User Manual 1756-SPESMNSEXT GuardLogix Controllers User Manual 1756-SPESMNSE GuardLogix Controllers User Manual 1756-ESMNRMXT GuardLogix Controllers User Manual 1756-ESMNRM GuardLogix Controllers User Manual 1756-ESMNSEXT GuardLogix Controllers User Manual 1756-ESMNSE GuardLogix Controllers User Manual 1756-ESMCAPXT GuardLogix Controllers User Manual 1756-ESMCAP GuardLogix Controllers User Manual 1756-L7x GuardLogix Controllers User Manual 1756-LSP GuardLogix Controllers User Manual 1756-L6x GuardLogix Controllers User Manual