Rockwell Automation 1440-DYN02-01RJ XM Dynamic Measurement Module Manuel d'utilisation
Page 99

Publication ICM-UM002F-EN-E - March 2013
99
I/O Data Tags
Apendix A
Module-defined Data Type: AB:1440_VDP:C:0
Member Name
Type
Default Display Style
Description
Ch0
AB:1440_VDP_ChConfig_Struct:C:0
Ch1
AB:1440_VDP_ChConfig_Struct:C:0
TachAutoTriggerEn
BOOL
Decimal
0 = Manual Trigger
1 = Auto Trigger (Default)
TachTriggerSlope
BOOL
Decimal
0 = Positive
1 = Negative (Default)
TachInhibitZeroPulseFault
BOOL
Decimal
0 = No pulses on tachometer produces fault
(Default)
1 = Inhibit zero pulses fault on tachometer
TachResponseTime
SINT
Decimal
0 = 2640.0 ms
1 = 220.0 ms (Default)
2 = 22.0 ms
TachFaultDelay
SINT
Decimal
1 to 64 seconds (Default = 11)
TachFaultLLimit
REAL
Float
-9,999,999 to 9,999,999 volts (Default = 2)
TachFaultHLimit
REAL
Float
-9,999,999 to 9,999,999 volts (Default = 18)
TachTriggerHysteresis
REAL
Float
0.0 to 50.0 (Default = 2.0)
If TachAutoTriggerEn is set to 0, this value is
volts. If TachAutoTriggerEn is set to 1, this
value is % of the peak-to-peak input signal.
TachTriggerLevel
REAL
Float
-9,999,999 to 9,999,999 volts (Default = 0)
TachPulsesPerRevolution
INT
Decimal
Default = 1
Alarm0En
BOOL
Decimal
0 = Disable (Default)
1 = Enable
Alarm1En
BOOL
Decimal
0 = Disable (Default)
1 = Enable
Alarm2En
BOOL
Decimal
0 = Disable (Default)
1 = Enable
Alarm3En
BOOL
Decimal
0 = Disable (Default)
1 = Enable
Alarm4En
BOOL
Decimal
0 = Disable (Default)
1 = Enable
Alarm5En
BOOL
Decimal
0 = Disable (Default)
1 = Enable
Alarm0SpeedRangeEn
BOOL
Decimal
0 = Disable (Default)
1 = Enable
Alarm1SpeedRangeEn
BOOL
Decimal
0 = Disable (Default)
1 = Enable
Alarm2SpeedRangeEn
BOOL
Decimal
0 = Disable (Default)
1 = Enable
Alarm3SpeedRangeEn
BOOL
Decimal
0 = Disable (Default)
1 = Enable