Configure XM Module in RSLogix 5000 Software
Chapter 3
3.
When finished, click one of these as needed.
• OK - Click to accept your edits and close the dialog box.
• Cancel - Click to close the dialog box without accepting your edits.
• Apply - Click to accept and apply your edits on any dialog and
continue editing.
Logic
Choose the relay activation logic. The relay can
monitor up to two alarms.
• A Only - Relay is activated when Alarm A meets or
exceeds the selected Alarm Status to Activate On
condition(s).
• A OR B - Relay is activated when either Alarm A or
Alarm B meets or exceeds the selected Alarm
Status to Activate On condition(s).
• A AND B - Relay is activated when Alarm A and
Alarm B meet or exceeds the selected Alarm Status
to Activate On condition(s).
Alarm ID A
Choose the first alarm that the relay will monitor. The
alarm must be from the same device as the relay.
Only enabled alarms appear in the Alarm ID A
list.
Alarm ID B
Choose the second alarm that the relay will monitor.
The alarm must be from the same device as the relay.
Only enabled alarms appear in the Alarm ID B
list.
Note: This parameter is dimmed when Logic is
set to A only.
Alarm Status to Activate On
Choose the alarm conditions that will cause the relay
to activate. You can select more than one.
• Normal - Activate the relay when the current
measurement is not in excess of any alarm limits.
• Danger - Activate the relay when the current
measurement is in excess of the danger level
limit(s).
• Xdcr Fault - Activate the relay when a transducer
fault is detected on the associated transducer.
• Tacho Fault - Activate the relay when the required
tachometer signal has not been detected and there
is no transducer fault.
• Alert - Activate the relay when the current
measurement is in excess of the alert level limit(s)
but not in excess of the danger level limit(s).
• Disarm - Activate the relay when the alarm is
disabled. If Setpoint Multiplication is on and the
setpoint multiplier is set to zero, the alarm will be
disabled and in the Disarm state.
• Module Fault - Activate the relay when a failure or
error is detected in the hardware or firmware, and
is preventing proper operation of the device.
In this field
Values are
Comments