Module-defined Data Type: AB:1440_VDP_AlarmConfig_Struct:C:0
Member Name
Type
Default Display Style
Description
LAlertLimit
REAL
Float
-999,999 to 999,999 (Default = -6)
HAlertLimit
REAL
Float
-999,999 to 999,999 (Default = 6)
LDangerLimit
REAL
Float
-999,999 to 999,999 (Default = -8)
HDangerLimit
REAL
Float
-999,999 to 999,999 (Default = 8)
Deadband
REAL
Float
0 to 9999 (Default = 0.1)
LimitMultiply
REAL
Float
0 to 10 (Default = 1.0)
SpeedLLimit
REAL
Float
0 to 9,999,999 (Default = 0)
SpeedHLimit
REAL
Float
0 to 9,999,999 (Default = 1000)
LimitMultiplyPeriod
INT
Decimal
0 to 65535 seconds (Default = 1.0)
Condition
SINT
Decimal
0 = Greater Than (Default)
1 = Less Than
2 = Inside Range
3 = Outside Range
MeasurementID
SINT
Decimal
0 = Ch 0 Overall (Default)
1 = Ch 1 Overall
2 = Ch 0 DC Bias/Gap
3 = Ch 1 DC Bias/Gap
4 = Ch 0 Band 0
5 = Ch 1 Band 0
6 = Ch 0 Band 1
7 = Ch 1 Band 1
8 = Ch 0 Band 2
9 = Ch 1 Band 2
10 = Ch 0 Band 3
11 = Ch 1 Band 3
12 = Speed
13 = SMAX Magnitude
14 = Ch 0 1X Magnitude
15 = Ch 1 1X Magnitude
16 = Ch 0 2X Magnitude
17 = Ch 1 2X Magnitude
18 = Ch 0 3X Magnitude
19 = Ch 1 3X Magnitude
20 = Ch 0 Not 1X
21 = Ch 1 Not 1X
22 = Ch 0 Sum Harmonics
23 = Ch 1 Sum Harmonics
24 = Ch 0 1X Phase
25 = Ch 1 1X Phase
26 = Ch 0 2X Phase
27 = Ch 1 2X Phase
28 = SMAX Phase
29 = Acceleration