Configuration data type – Rockwell Automation 1440-DYN02-01RJ XM Dynamic Measurement Module Manuel d'utilisation
Page 96

96
Publication ICM-UM002F-EN-E - March 2013
Appendix A I/O Data Tags
Configuration Data Type
Module-defined Data Type: AB:1440_VDP_ChConfig_Struct:C:0
Member Name
Type
Default Display Style
Description
OverallFilterEN
BOOL
Decimal
0 = None
1 = Low Pass Filter
SynchronousModeEN
BOOL
Decimal
0 = Asynchronous (Default)
1 = Synchronous with tach
XdcrPower
SINT
Decimal
0 = Off (Default)
1 = IEPE
2 = +24V
3 = -24V
4 = Bias Current
XdcrSensitivityUnits
SINT
Decimal
0 = mV/ mil (Default)
1 = mV/ in/s
2 = mV/ g
3 = mV/ psi
4 = V/ V
5 = mV/ mm/s
6 = mV/ µm
8 = mV/ mbar
9 = V/ g
XdcrLLimit
REAL
Float
-24.0 to 24.0 volts (Default = -18.0 volts)
XdcrHLimit
REAL
Float
-24.0 to 24.0 volts (Default = -2.0 volts)
XdcrSensitivity
REAL
Float
Default = 200.0
(XdcrSensitivityUnits selection determines
the units)
FullScale
REAL
Float
Default = 10.0
(FullScaleUnits selection determines the
units)
FullScaleUnits
SINT
Decimal
0 = mil (Default)
1 = in/s
2 = g
3 = psi
4 = volt
5 = mmps
6 = µm
8 = mbar
SignalMeasurementType
SINT
Decimal
0 = RMS
1 = Calculated peak
2 = Calculate pk-pk
3 = True peak
4 = True pk-pk (Default)
FFTWindowType
SINT
Decimal
0 = Rectangular
1 = Hamming
2 = Hanning (Default)
3 = Flat Top
4 = Kaiser Bessel