European hazardous location approval – Rockwell Automation 1440-DYN02-01RJ XM Dynamic Measurement Module Manuel d'utilisation
Page 15

Publication ICM-UM002F-EN-E - March 2013
15
Installing the XM Dynamic Measurement Module
Chapter 2
European Hazardous Location Approval
The following applies when the product bears the Ex Marking.
This equipment is intended for use in potentially explosive atmospheres as defined
by European Union Directive 94/9/EC and has been found to comply with the
Essential Health and Safety Requirements relating to the design and construction
of Category 3 equipment intended for use in Zone 2 potentially explosive
atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured
by compliance with EN 60079-15 and EN 60079-0.
ATTENTION
This equipment is not resistant to sunlight or other sources of
UV radiation.
WARNING
This equipment must be mounted in an ATEX certified enclosure
with a minimum ingress protection rating of at least IP54 (as
defined in IEC60529) and used in an environment of not more
than Pollution Degree 2 (as defined in IEC 60664-1) when
applied in Zone 2 environments. The enclosure must utilize a
tool removable cover or door.
WARNING
This equipment must be used within its specified ratings
defined by Rockwell Automation.
WARNING
Provision must be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 140% of the
rated voltage when applied in Zone 2 environments.
WARNING
This equipment must be used only with ATEX-certified
Allen-Bradley terminal bases.