Instance Attributes
Services
Table B.52 Vector Measurement Object Instance Attributes
Attr ID
Access
Rule
Name
Data Type
Description
Semantics
3
Get
Magnitude
Value
REAL
The measured magnitude
value.
4
Get
Phase Value
REAL
The measured phase
value.
Degrees
Note: Not valid for instances 5
and 6.
5
Get
Status
BOOL
Indicates if a fault or
alarm has occurred.
0 = Operating without alarms of
faults.
1 = Alarm or fault condition
exists. The
Value attributes
may not represent the actual
field value.
6
Get
Magnitude Data
Units
ENGUNIT
The units context of the
Magnitude Value
attribute.
This setting is determined by the
Channel Object’s
Output Data
Units setting (see
).
7
Get
Speed Value
REAL
The speed at which the
magnitude and phase are
measured.
Instances 1 and 2 use 1X
machine speed.
Instances 3 and 4 use 2X
machine speed.
Instances 5 and 6 use 3X
machine speed.
The value is only valid when
synchronous sampling mode is
selected for the corresponding
channel.
8
Get
Speed Data
Units
ENGUNIT
The units context of the
Speed Value attribute.
See DeviceNet Specification
Volume 1 Appendix K.
This is set to Orders.
Table B.53 Vector Measurement Object Services
Service
Code
Class/Instance Usage
Name
Description
0E
h
Instance
Get_Attribute_Single
Returns a single attribute.