Chapter 3 Configure XM Module in RSLogix 5000 Software
1.
From the Module Properties dialog box, click the Band tab.
2.
Click the Channel that you want to configure.
3.
Configure the parameters, as necessary.
In this field
Values are
Comments
Channel Name
A descriptive name for the channel.
This can be entered on the Channel tab.
Configure the Channel Properties on page 64
.
Measurement Mode
Choose the measurement (or calculation) performed to
produce the Band Value.
• Band Overall - The band value is the square root of
the sum of the squares (RSS) of the amplitude
values for the bins that make up the band.
• Maximum Peak - The band value is equal to the
maximum bin amplitude found within the band.
Frequency Maximum
Enter the upper limit of the range of spectrum bins to
be included in the band measurement, and the
frequency units (Hz or Orders). Set the value using the
table below.
This value must be greater than the Band
Frequency Minimum.
Frequency Minimum
Enter the spectrum bin with the least frequency to be
included in the band measurement.
Sampling
Mode
Spectrum
Frequency
Max Units
Band Units
Band
Frequency
Max
Synchronous
Orders
Hz
0...5000
Orders
0.01...200
Asynchronous
Hz
Hz
0...20,000
Orders
0.01...200