Configure XM Module in RSLogix 5000 Software
Chapter 3
1.
From the Module Properties dialog box, click the Channel tab.
2.
Click the Channel that you want to configure.
3.
Configure the parameters as necessary.
In this field
Values are
Comments
Channel Name
Enter a descriptive name for the channel.
The channel name is not sent to the XM
module.
Power
Choose the type of power supplied to the transducer.
• Off
• IEPE (externally supplied)
• -24V (externally supplied)
• +24V (externally supplied from the terminal base)
• Bias Current (externally supplied)
See Connecting the Transducer on page 34
for
wiring requirements.
See table below.
Approximate Expected Bias Voltage (V DC)
Power
Normal Connected Sensor
Open
Circuit
Short
Circuit
Unconnected
Sensor
DC Low
Limit Default
DC High Limit
Default
Off
sensor bias voltage (-10...10V DC typical)
2
0
2
-10
10
IEPE
sensor bias voltage (12...20V DC typical)
24
0
24
12
20
+24V
sensor bias voltage (1...20V DC typical)
2
0
2
1
20
-24V
sensor bias voltage (-14...-8V DC typical)
2
0
2
-14
-8
Bias Current
0.47V with 2000 ohm coil
13
0
13
0.2
2