Rockwell Automation 1440-DYN02-01RJ XM Dynamic Measurement Module Manuel d'utilisation
Page 37

Publication ICM-UM002F-EN-E - March 2013
37
Installing the XM Dynamic Measurement Module
Chapter 2
Figure 2.15 Non-contact Sensor to Channel 1 Wiring
Connecting a Passive Transducer
The following figures show the wiring of a passive transducer, such as a
velocity sensor, to the terminal base unit.
TYPICAL WIRING FOR NON-CONTACT SENSOR
TO XM DYNAMIC MEASUREMENT MODULE CHANNEL 1
Channel 1 Input Signal
Signal Common
Shield
-24V DC
ATTENTION
You may ground the cable shield at either end of the cable. Do
not ground the shield at both ends. Recommended practice is to
ground the cable shield at the terminal base and not at the
transducer. Any convenient Functional Earth terminal may be
used. See
Terminal Block Assignments on page 28
.
IMPORTANT
The module does not power the sensor. It measures only the
input voltage.
IMPORTANT
Make certain the
Power parameter is set to Bias Current.