Services, Device mode object (class id 320h), Class attributes – Rockwell Automation 1440-DYN02-01RJ XM Dynamic Measurement Module Manuel d'utilisation
Page 130: Device mode object (class id 320

130
Publication ICM-UM002F-EN-E - March 2013
Appendix B CIP Objects
Services
(1)
Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.
Device Mode Object
(Class ID 320
H
)
The Device Mode Object is used to control access to the configuration
parameters in the module. This object’s Device Mode attribute must be in
PROGRAM mode to allow the module’s configuration parameters to be Set
(see Services). Attempts to set the configuration parameters while the Device
Mode is in RUN mode will return an error. Note that the module collects
measurements while in RUN mode but not while it is in PROGRAM mode.
Class Attributes
The Device Mode Object provides no class attributes.
104
Get
Very High HPF
Corner Frequency
REAL
The frequency, in Hz, of
the "Very high"
Low
Cutoff Frequency option
for attribute 5.
Hz
105
Get
Channel Alarm
Status
USINT
Summary of the Alarms
configured for this
channel.
0 = Normal
1 = Alert (alarm)
2 = Danger (shutdown)
3 = Disarm
Table B.29 Channel Object Instance Attributes
Attr ID
Access
Rule
Name
Data Type
Description
Semantics
Table B.30 Channel Object Services
Service
Code
Class/Instance Usage
Name
Description
0E
h
Instance
Get_Attribute_Single
Returns a single attribute.
10
h
Instance
Set_Attribute_Single
Sets a single attribute.
(1)