Rockwell Automation 1440-DYN02-01RJ XM Dynamic Measurement Module Manuel d'utilisation
Page 39

Publication ICM-UM002F-EN-E - March 2013
39
Installing the XM Dynamic Measurement Module
Chapter 2
Connecting a Powered Sensor
The following figures show the wiring of a powered sensor, such as the Model
580 Vibration Pickup, to the terminal base unit.
Figure 2.18 Powered Sensor to Channel 0 Wiring
ATTENTION
You may ground the cable shield at either end of the cable. Do
not ground the shield at both ends. Recommended practice is to
ground the cable shield at the terminal base and not at the
transducer. Any convenient Functional Earth terminal may be
used. See
Terminal Block Assignments on page 28
.
IMPORTANT
Make certain the
Power parameter is set to +24V so power is
provided to the transducer.
TYPICAL WIRING FOR MODEL 580 VIBR ATION PICKUP
TO XM DYNAMIC MEASUREMENT MODULE CHANNEL 0
Channel 0 Input Signal