Appendix B CIP Objects
Instances
There are 16 instances of this object.
Instance Attributes
IMPORTANT
Alarms 6 through 15 are not available when the module is
configured in the RSLogix 5000 software.
Table B.24 Alarm Object Instance Attributes
Attr ID
Access
Rule
Name
Data Type Description
Semantics
3
Get
Alarm Status
3 BITS
The current status of the
alarm.
0 = Normal
1 = Alert (alarm)
2 = Danger (shutdown)
3 = Disarm
4 = Xdcr Fault
5 = Module Fault
6 = Tachometer Fault
4
Get/Set
Alarm Enable
BOOL
Indicates whether this
alarm object is enabled.
0 = Disabled
1 = Enabled
5
Get
Type
USINT
Type of Alarm
0 = Magnitude
1 = Vector
6
Get
Threshold Units
USINT
Indicates whether the
thresholds and deadband
value are specified in
units of measure. Not
applicable to vector
alarms.
Set to 1
1 = Measurement units
7
Get/Set
AlarmCondition
USINT
Indicates on which side of
the threshold values the
alarm and danger
conditions exist. Not
applicable to vector
alarms.
0 = Greater than
1 = Less than
2 = Inside range
3 = Outside range
8
Get/Set
AlarmHAlertLimit
REAL
The threshold value for
the alert state of the
alarm. (For range
conditions, this is the
greater threshold value.)
9
Get/Set
AlarmHDangerLimit
REAL
The threshold value for
the Danger state of the
alarm. (For range
conditions, this is the
greater threshold value).