136
Publication ICM-UM002F-EN-E - March 2013
Appendix B CIP Objects
Services
(1)
Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.
12
Get/Set
Logic
USINT
Indicates the number of
associated alarms that
must have a status value
specified by
Alarm Level
in order to activate the
relay.
0 = Ignore
Alarm Identifier B
and activate the relay based on
the status of
Alarm Identifier
A.
1 = Activate the relay if the
status of either
Alarm
Identifier A or B matches any
of the statuses specified by
Alarm Level.
2 = Activate the relay if the
status of both
Alarm Identifier
A and B match any of the
statuses specified by
Alarm
Level.
14
Get
Relay Installed
BOOL
Indicates whether an
actual relay is associated
with this instance.
0 = Not installed
1 = Installed
15
Get/Set
Idle Hold
USINT
Hold relay state during
reconfiguration.
0 = Relay is deactivated while
module is in Program mode.
1 = Relay retains last state
while in Program mode.
Table B.36 Relay Object Instance Attributes
Attr ID
Access
Rule
Name
Data Type
Description
Semantics
Table B.37 Relay Object Services
Service
Code
Class/Instance Usage
Name
Description
05
h
Class/Instance
Reset
Resets latched relay.
0E
h
Class/Instance
Get_Attribute_Single
Returns a single attribute.
10
h
Class/Instance
Set_Attribute_Single
Sets a single attribute.