Instance attributes – Rockwell Automation 1440-DYN02-01RJ XM Dynamic Measurement Module Manuel d'utilisation
Page 135

Publication ICM-UM002F-EN-E - March 2013
135
CIP Objects
Appendix B
Instance Attributes
Table B.36 Relay Object Instance Attributes
Attr ID
Access
Rule
Name
Data Type
Description
Semantics
3
Get
Relay Status
BOOL
The current status of the
relay.
0 = Off
1 = On
4
Get/Set
Relay Enable
BOOL
Indicates whether this
relay object is enabled.
0 = Disabled
1 = Enabled
5
Get/Set
Latch Enable
BOOL
Indicates whether this
relay latches (requires a
reset command to
deactivate).
0 = Nonlatching
1 = Latching
6
Get/Set
Failsafe Enable
BOOL
Indicates whether this
relay is normally
energized (activated
during power loss).
0 = Non-failsafe (not normally
energized)
1 = Failsafe (normally energized)
7
Get/Set
Delay
UINT
The time period that the
voting logic must be true
before the relay is
activated.
0...65.535 seconds
(specified in milliseconds)
8
Get/Set
Name
STRING2
A name to help identify
the relay.
18 characters maximum
9
Get/Set
Alarm Level
BYTE
Specifies what alarm
status values will cause
the relay to activate.
0 = Normal
1 = Alert
2 = Danger
3 = Disarm
4 = Xdcr Fault
5 = Module Fault
6 = Tachometer Fault
10
Get/Set
Alarm Identifier A
EPATH
Identifies the first alarm
status the relay monitors.
See Parameter Object instances
26 to 30.
11
Get/Set
Alarm Identifier B
EPATH
Identifies the second
alarm status the relay
monitors.
See Parameter Object instances
31 to 35.