Chapter 2 Installing the XM Dynamic Measurement Module
Connecting the Power Supply
The power supply to the module is nominally 24V DC. The Class 2 power
supply connection provides power to the device and other XM modules
located on the DIN rail.
When wiring the DC input power supply to the terminal base unit, connection
may be made as shown in Figure 2.6. Also refer to Figure 2.1 on
.
Tachometer
34
Tach/Signal In (+)
Tachometer transducer/signal input, positive side
35
Tach/Signal In (-)
Tachometer transducer/signal input, return
36
Functional Earth
Shield return for Tach/Signal cable
Connection to DIN rail ground spring or panel mounting hole
37
Tachometer 24V (-)
Tachometer power supply output, negative side
-24V relative to Signal Common (terminal 41)
38
Tachometer 24V (+)
Tachometer power supply output, positive side
39
TACH Buffer
Isolated from terminal 34 by a resistor
40
Tach/Signal (-)
Return for terminal 39 or connect to terminal 41 for powered Tach
transducer when TACH Buffer is not used
41
Signal Common
Power
42
Not Connected
43
24 V Common
44
+24 V In
Connection to external +24V power supply, positive side
45
24 V Common
Connection to external +24V power supply, negative side (internally
DC-coupled to signal ground)
Bussed Tach
46
Tach/Signal Out (-)
Used to daisy chain tachometers
Connect to terminal 45 or 41 for a powered Tach transducer (left most
module only)
47
Tach/Signal Out (+)
Used to daisy chain tachometer to additional terminal bases
Connect daisy chain to terminal 34 of next terminal base
48
Tach/Signal Out (-)
Used to daisy chain tachometer
Connect daisy chain to terminal 35 of next terminal base
49
Not Connected
50
Not Connected
51
Not Connected
Terminal Block Assignments
No.
Name
Description