Chapter 2 Installing the XM Dynamic Measurement Module
Figure 2.5 1440-TBS-J Terminal Base Unit
Terminal Block Assignments
The terminal block assignments and descriptions for the Dynamic
Measurement module is shown below.
IMPORTANT
The terminal block assignments are different for different XM
modules. The following table applies only to the 1440-TBS-J
terminal base unit. Refer to the installation instructions for the
specific XM module for its terminal assignments.
WARNING
If you connect or disconnect wiring while the field-side power
is on, an electrical arc can occur. This could cause an explosion
in hazardous location installations. Be sure that power is
removed or the area is nonhazardous before proceeding.
Cat. No. 1440-TBS-J
Terminal Block Assignments
No.
Name
Description
Channel 0
0
Xducer 0 (+)
Vibration transducer 0 connection
1
Xducer 0 (-)
Vibration transducer 0 connection
2
Functional Earth
Connection to DIN rail ground spring or panel mounting hole
3
Xducer 0 Pwr 24V (-)
Transducer power supply output, negative side; used to power external
sensor
-24V relative to Signal Common (terminal 41)
4
Xducer 0 Pwr 24V (+)
Transducer power supply output, positive side; used to power external
sensor
5
Buffer 0 (+)
Vibration signal 0 buffered output
6
Buffer Output RTN
Vibration buffered output return
7
Not Connected