93 hot water but no central heating, Eau chaude mais pas de chauffage – Rinnai Q130SN Manuel d'utilisation

Page 93

Advertising
background image

Installation & Servicing Instructions Rinnai Q-Series

93

hot water but no

central heating

-Key of the central

heating program is not

switched on

room thermostat (on/

off) is not giving any

signal to the boiler

RS100 with outdoor

sensor

(Room sensor-On)

17.2 Hot water but no central heating

Eau chaude mais pas de chauffage central

three-port valve is not circulating to

central heating position

Check timer program and set room
temperature

check room thermostat

outdoor temperature is higher than 70°F,
depending upon the Eco-temperature set
(70°F is the default). Check Info chapter
Step 7 or temperature is higher than the
Eco temperature set (see RS100 installation
instructions).

check wiring, replace the three-port valve
motor

switch on central heating program

eau chaude mais

pas de chauffage

La touche

du

programme de chauffage

central n’est pas activée

le thermostat d’ambiance

(on/off) n’envoie aucun

signal à la chaudière

RS100 avec capteur

extérieur (capteur

d’ambiance sur On)

la vanne en T ne distribue pas en

position de chauffage central

Vérifiez le programme de la minuterie et régler
la température de la pièce

vérifiez le thermostat d’ambiance

la température extérieure est supérieure à 70°F
(21°C), selon la consigne d’éco-température

(70°F est la valeur par défaut). Vérifier l’étape
7 du chapitre Info ou si la température est
supérieure à la consigne d’éco-température
(voir les instructions d’installation du RS100).

vérifiez le câblage, remplacez le moteur de la
vanne trois voies

activez le programme de chauffage central