42 8 electrical connections – Rinnai Q130SN Manuel d'utilisation

Page 42

Advertising
background image

Installation & Servicing Instructions Rinnai Q-Series

42

8

Electrical connections

The electrical connections to the boiler must be made in accordance with all applicable
local codes and the latest revision of the National Electrical Code, ANSI/NFPA-70.
Installations should also conform with CSA C22.1 Canadian Electrical Code Part 1
if installed in Canada.

Devices such as, outdoor sensor, room thermostat or temperature control, 3-way
valve (except Q175CN/Q175CP), temperature sensor or thermostat and an external
pump are all connected to the internal connection terminal. The connection terminal
is situated in the Control Tower.

Connecting incoming power
Lead the cable through the back part of the boiler using a strain relief and lead the
cable through the cable supports to the Control Tower.
Connect a power supply cable to the cable harness terminal strip that connects to
both the power switch on the front of the Control Tower and the terminal strip with
positions 1,2, and 3 on the inside of the Cotnrol Tower.

The boiler must be electrically grounded in accordance with local codes, or

in absence of local codes, with the National Electrical Code, ANSI/INFPA 70

and/or the CSA C22.1, Electrical Code.
RISK OF ELECTRIC SHOCK.
Once the main power supply is on then there is 120V on terminals 1 to 12 if the main
switch at the front of the Control Tower is switched on.

- No changes may be made to the wiring of the boiler.

- All connections should be designed in accordance with the applicable

regulations.

- Label all wires prior to disconnection when servicing controls. Wiring errors

can cause improper and dangerous operation.

- Verify proper operation after operation servicing.

The Rinnai room thermostat and controls must be connected to their allocated

connections. All other types or makes of room thermostats or controls which

are used must have a Volt free contact.

When using an on/off thermostat or control, it is possible that an anticipating resistance

must be calibrated in order to prevent too high temperature fluctuations. As a standard
rule this means mercury thermostats. This resistance wire is present in the Control
Tower and must be connected to clamps 23 and 27. The anticipating resistance in
the room thermostat has to be set at 0.11 A.
For more detailed questions regarding the components which are not supplied, the
distributor should be contacted.

Connection terminal Q-Series

Connection terminal

figure 21

120 V

olts for

external pump

main power

supply

120 V

olts for

external control

120 V

olts

internal or external

three-way valve

motor

and

tank sensor

Bus

room thermostat

On/of

f thermostat or

control (V

olt free)

AR

V12 outdoor

sensor

External safety

contact

24 V

olts

maximum 100 mA

CAUTION

CAUTION

CAUTION
Make sure that the power consumption of each of the terminals
4-5-6, 7-8-9 and10-11 does not exceed 230W or 2 Amp.

!

CAUTION

NOTICE

i

CAUTION

!

CAUTION

Advertising
Ce manuel est liée aux produits suivants: