Installation & Servicing Instructions Rinnai Q-Series

73

disconnect voltage

from the boiler and

check the fuse F2

check the 24 Volt

connection

check the

disconnected

components for

short-circuiting

rectify the short-

circuit or replace

the short-circuited

component

24 Volt short-circuit

as a result of a 24 Volt short-circuit inside or
outside the boiler the fuse F2 will have blown.
This fuse is placed in the control unit and
can be seen after the black covering cap is
removed.

remove all plugs with 24 Volt connections
such as: fan, pump, any three-port valve and
24 Volt plug to the connecting block.

switch on power again to the control unit with
the components disconnected. Reconnect the
components, which have been checked and
are working.

16.2.2

Erreur / Error 01

débranchez le courant

de la chaudière et

vérifiez le fusible F2

rectifiez le court-

circuit ou remplacez

le composant court-

circuité

vérifiez le

branchement en 24

Volt

vérifiez les courts-

circuits sur les

composants

débranchés

Court-circuit en 24 Volt

Il résulte d’un court-circuit en 24 Volt à
l’intérieur ou à l’extérieur de la chaudière, que
le fusible F2 grille. Ce fusible est placé dans
l’appareil de contrôle et se voit en retirant le
couvercle noir.

Retirez toutes les fiches avec raccordement
en 24 Volt, comme : ventilateur, pompe,

vannes trois voies et fiche 24 Volt au bloc
de raccordement.

rallumez l’alimentation électrique sur l’appareil
de contrôle avec tous les composants
débranchés. Rebranchez les composants qui

ont été vérifiés et qui fonctionnent.