Installation & Servicing Instructions Rinnai Q-Series

68

check flow

through the

installation

16.1.2

Blocage / Block 11

see the installation instructions for the hydraulic
connections to the boiler
(3-Way-Thermostatic valve, Plumbing Kit

installed?)

maximum average

T of supply and return

sensor for central heating is repeatedly
exceeded. Operation is normally possible
for the hot water supply during the block.
The pump continues to operate at minimum
capacity during the block.

possible causes: (radiator) shut-off valves

closed or blocked water filter

check pump height.

check minimum and maximum Temperature
difference in Parameter Step 46 + 47.

activeted room sensor (RS101) in non leading

room (closed thermostatic radiator valves?)

vérifiez le débit

dans toute

l’installation

consultez les instructions d’installation pour
les raccordements hydrauliques à la chaudière
(vanne thermostatique 3 voies, kit de plomberie

installés ?)

Le

T maximum moyen du capteur

d’alimentation et de retour du le chauffage
central a été dépassé plusieurs fois. Pendant
le blocage, le fonctionnement normal de
l’alimentation en eau chaude est possible. La
pompe continue à fonctionner à sa capacité
minimale pendant le blocage

causes possibles : (radiateur) vannes d’arrêt

fermées ou filtre à eau bloqué

vérifiez la hauteur de la pompe.

vérifiez la différence de température minimale
et maximale dans Paramètre Etape 46 + 47.

capteur d’ambiance activé (RS101) dans une
pièce non centrale (vannes thermostatiques

de radiateur fermées ?)