Installation & Servicing Instructions Rinnai Q-Series

35

Terminal positions PVC figure 17

Equivalent friction loss of PVC/CPVC

table 8

Fittings or Piping Equivalent

feet

m

45 degree elbow

3

0.91

90 degree elbow

6

1.83

plastic pipe per foot

1

0.30

concentric vent kit

3

0.91

12" (300 mm)

minimum

12" (300 mm)

minimum

12" (300 mm)

minimum

INTAKE

EXHAUST

12" (300 mm)

minimum

12" (300 mm)

minimum

6.7.5

Dimensioning of the exhaust and air intake duct

The wall mounted boiler must be vented and supplied with combustion and

ventilation air as described in this section.

Ensure the vent and air piping and the combustion air supply comply with

these instructions regarding vent system, air system, and combustion air

quality.

Inspect finished vent and air piping thoroughly to ensure all are airtight and

comply with the instructions provided and with all requirements of applicable

codes.

Failure to provide a properly installed vent and air system may cause severe

personal injury or death.

Use only the material listed in Rinnai's vent documentation for vent pipe, and

fittings. Failure to comply could result in severe personal injury, death or

substantial property damage.

Installation must comply with local requirements and with the National Fuel

Gas Code, ANSI Z223.1 for U.S installations or CSA B 149.1 for Canadian

installations.

For closet and alcove installation, CPVC material, instead of PVC, must be

used in a closet/alcove structure. Failure to follow this warning could result

in fire, personal injury, or death.

All vent pipes must be connected and properly supported, and the exhaust

must be pitched a minimum of a 1/4” inch per foot back to the boiler (to allow

drainage of condensate). Please refer to the venting manufacturer's manual

to see if a larger pitch is required for specific venting systems. The venting

system manufacturer's required venting pitch must always be followed if

larger than 1/4 inch.

Combustion air piping from the outside MUST BE used. For direct vent

installations, use of combustion air from indoor rooms using louvers,

plenums, or any other devices is not authorized.

See the Rinnai Boiler Applications Manual for further information on venting.

!