Rinnai Q130SN Manuel d'utilisation

Page 89

Advertising
background image

Installation & Servicing Instructions Rinnai Q-Series

89

check the data

in Error mode

check the wiring

the wiring is OK

but the error is

repeated

replace the

sensor

vérifiez les données

en mode Erreur

le câblage est

OK, mais l’erreur

persiste

vérifiez le câblage

remplacez le

capteur

* = variable value
**= x3415=BTH/hr

1 = 31
2 = 00
3 = 230
4 = xx*
5 = 00**
6 = xx*

1 error
2 operational
status

3 flow temp.
4 return temp.
5 kW burner
6 % pump

1 erreur
2 opérationnel
état
3 temp. de départ
4 temp. de retour
5 Brûleur kW
6 % pompe

* = valeur variable
**= x3415=BTU/hr

1 = 14
2 = 00
3 = -22
4 = xx*
5 = 00**
6 = xx*

contact for return sensor T2 open

boiler data during error

check the wiring for the sensor to make sure
it is not broken

connect the wiring from the return sensor with
one another as a result of which Error 32
occurs

16.2.18 Erreur / Error 37

contact du capteur de retour T2 ouvert

données de la chaudière pendant une erreur

vérifiez le câblage du capteur pour s’assurer
qu’il n’est pas cassé

raccordez le câblage du capteur de retour
avec un autre, qui provoque l’Erreur 32