Installation & Servicing Instructions Rinnai Q-Series

75

check the data

in Error mode

1 error
2 operational
status
3 supply temp.
4 return temp.
5 kW burner
6 % pump

there is a temperature

difference between

supply (3) and

return (4)

no temperature

difference between

supply (3) and

return (4)

boiler has gone out

after ignition

ionisation flow,

ionisation cable or the

O

2

setting

boiler has not been

able to ignite any gas

or has not received any

gas

check whether:
- the gas valve is

open;

- there is power to the

gas valve;

- that the gas valve

opens

no flame formation

boiler data during error

1 = 02
2 = 02
3 = xx*
4 = xx*
5 = xx**
6 = xx*

due to insufficient

ionisation the burner

has gone out after

ignition

boiler tries to start

6 times with an

increasing starting

load after the safety

time

the minimum gas

preliminary pressure

during the start must

be a minimum of

7"W.C. (17 mbar),

check the 24 Volts in

the gas during ignition

block’s open position

* = variable value
**= x 3451 = BTU/hr

the minimum

ionisation flow should

be 4 µA, the O

2

should

be 4.7 %

Erreur / Error 02