Installation & Servicing Instructions Rinnai Q-Series

71

check the boiler

pump

no water flow can be detected through the
controller. De-aeration cycle is started. When

water flow is detected during this cycle, the
de-aeration cycle is terminated and the burner
is released.

check the installation for the presence of air;
If there is a secondary pomp installed and
it is not hydraulicly seperated could cause
pressure differences.

check that the pump is functioning and/or that
the water pressure sensor is working properly;
Polluted pump;
Wiring of pump or water pressure sensor;

16.1.6

Blocage / Block 85

16.1.7

Blocage / Block 86

check the main

power supply

The frequence of the power supply deviates
more than 2,5Hz (<57,5Hz, >62,5Hz)

Aucun débit d’eau ne peut être détecté par
le contrôleur. Le cycle de désaération a
commencé. Si pendant ce cycle un débit d’eau
est détecté, le cycle de désaération se termine
et le brûleur est libéré.

Vérifiez la présence d’air dans l’installation ;
Si une pompe secondaire est installée et
n’est pas séparée hydrauliquement, elle peut
provoquer des différences de pression.

vérifiez que la pompe fonctionne et/ou que
le capteur de pression d’eau fonctionne cor-
rectement ;
Pompe polluée ;
câblage de la pompe ou capteur de pression
d’eau

La fréquence de ‘alimentation électrique
diffère de plus de 2,5 Hz (< 57,5 Hz, > 62,5 Hz)

vérifiez l’alimentation

électrique principale

contrôlez la

pompe de la

chaudière