Installation & Servicing Instructions Rinnai Q-Series

52

Parameter Mode

PARA

FACTORY

DESCRIPTION

RANGE

.

.

.

.

1

186°F

maximum supply temperature CH

68 - 176°F

2*

00

type of CH installation:

01 DO NOT USE

radiators with large surface areas or underfloor heating as additional heating:

T max. supply 158°F K factor heating curve 1.8; gradient 10°F/min; gear differential 10°F

02

under floor heating with radiators as additional heating:

T max. supply 140°F; K factor heating curve 1.5; gradient 8°F/min; gear differential 8°F

03

full under floor heating:

T max. supply 122°F; K factor heating curve 1.0; gradient 6°F/min; gear differential 6°F

04

3

max.

maximum power CH in kW (.. x3415 = .. BTU/hr)

min-max

4*

00

control principal with on / off thermostat:
100 % on / off thermostat

00

100 % on / off weather dependant

01

5*

2.3

heating curve K-factor (see also heating curve graph)

0.2 - 3.5

6*

1.4

heating curve exponent (see also heating curve graph)

1.1 - 1.4

7*

14°F

heating curve climate zone (see also heating curve graph)

-4 - 32°F

10*

0°F

fine adjustment heating curve day temperature

-8 to 10°F

11*

0°F

fine adjustment heating curve night temperature

-8 to 10°F

14

10°F/min.

gradient speed °F/min.

0 - 28°F/min.

15*

00

Booster after night decrease*:
no

00

yes

01

23

26°F

Frost Temperature

-4 to 50°F

27

32°F

Minimum T-set CH

32 - 158°F

31

146°F (154°F)

DHW tank temperature with external tank sensor

104 - 176°F

36

01

Type of three way valve DHW tank
VC 2010 / VC 8010

00

VC 6940

01

43

max.

Maximum power DHW in kW (.. x3415 = .. BTU/hr)

min-max

49

100%

Maximum pump capacity heating

40-100 %

73

0

Altitude and venting CFT. See chapter 6.7.7

0 - 100

89

00

Address of boiler in cascade
No function

-01

Bus thermostat

00

Cascade boiler 2 to 8

01 - 07

90

01

Display reading
°C and Bar

00

°F and PSI

01

.

.

.

.

Info Mode

INFO

FACTORY

DESCRIPTION

RANGE

.

.

.

.

1

°F

supply water temperature T1

4

°F

return water temperature T2

5

°F

DHW temperature T3

6

°F

T3-set from BrainQ

7

°F

outdoor temperature T4

8

°F

flue gas temperature T5 (optional sensor)

16

%

actual power in %

17

kW

actual power in kW (.. x3415 = .. BTU/hr)

18

kW

actual load in kW (.. x3415 = .. BTU/hr)

20

indication bus communication

21

GJ

consumption total in GJ (.. x 33 = .. m3)

22

GJ

consumption CH in GJ (.. x 33 = .. m3)

23

GJ

consumption DHW in GJ (.. x 33 = .. m3)

24

h

total number of burner run hours

25

h

number of burner run hours CH

26

h

number of burner run hours DHW

32

h

total number of hours counter

37

h

total number of run hours pump CH and DHW

46

h

within how many hours is service required

.

.

.