Installation & Servicing Instructions Rinnai Q-Series

80

remove the voltage from

the boiler and check

fuse F2

check the 24 Volt

connections

check the disconnected

parts for wear and tear

rectify the short-circuit

or replace the short-
circuited component

short-circuit 24 Volt

due to the 24 volt short-circuit inside or
outside the boiler, fuse F2 has blown. This
fuse is positioned in the control unit and can
be seen when the black covering lid has been
removed.

remove all plugs with 24 volt connections such
as: fan, pump, any three-port valve and 24 volt
plug to the connecting block

reconnect power to the control unit with the
disconnected parts. Reconnect the parts
which have been checked and are working
properly.

16.2.9

Erreur / Error 12

débranchez le courant

de la chaudière et

vérifiez le fusible F2

vérifiez les

branchements en 24

Volt

vérifiez l’usure ou une

déchirure sur les pièces

débranchées

rectifiez le court-

circuit ou remplacez

le composant court-

circuité

court-circuit en 24 Volt

Il résulte d’un court-circuit en 24 Volt à l’intérieur
ou à l’extérieur de la chaudière, que le fusible
F2 grille. Ce fusible est placé dans l’appareil de
contrôle et se voit en retirant le couvercle noir.

retirez toutes les fiches avec raccordement
en 24 Volt, comme : ventilateur, pompe,

vannes trois voies et fiche 24 Volt au bloc de
raccordement

rallumez l’alimentation électrique sur l’appareil
de contrôle avec les pièces débranchées.

Rebranchez les pièces qui ont été vérifiées
et qui fonctionnent correctement.