1 testing for gas leaks, 2 testing the ignition safety shut off device – Rinnai Q130SN Manuel d'utilisation

Page 56

Advertising
background image

Installation & Servicing Instructions Rinnai Q-Series

56

13.1 Testing for gas leaks

Prior to start-up of the boiler you must check the external tightness of the gas supply

valve and confirm this in the start-up report.

- Cover endangered positions before leak testing.

- Do not spray the leak testing agent onto cables, plugs, electrical

connection lines or electronic circuit boards. Do not allow it to drip onto

them either.

Leaks may be caused to pipes and screw connections during commissioning

and maintenance activities.

- Carry out a proper leak test.

- Only use approved leak detection agents for leak detection.

-

Disconnect the heating system from the power supply.

-

Check the exterior tightness of new conduit sections up to and including the direct

sealing point on the gas burner fitting. The maximum test pressure allowed on

the input of the gas burner fitting is 14 inch W.C. (35mbar).

13.2 Testing the Ignition Safety shut off device

-

Switch off system using the Central Heating button and the DHW button

-

Disconnect the plug and socket connection of the ionization cable.

-

Switch on the sytem using the Central Heating button and the DHW button.

-

Press the MODE-button for 5 seconds.

-

The display will show COdE followed by an arbitrary number;

-

Select by means of the + or the - button the code C123;

- Press the Store-button to confirm the code (code blinks 1 x);

-

Press the MODE-button until SERV is shown;

-

Press the STEP-button once until 1 is shown;

alternately 1 and OFF will be shown.

-

Press the + button once;

Check if the boiler does one start-up attempt and four restart attampts.

After the last start-up attempt, the boiler will lock out. The gas valve is shut off.

The E02 code is blinking in the display.

-

Connect the plug and socket connection of the ionisation cable.

-

Press the reset button.

-

Check if the boiler starts-up.

Do not touch the inside of the ignition cable while it is disconnected during

start up of the boiler.

!

WARNING

!

DANGER

CAUTION

Advertising
Ce manuel est liée aux produits suivants: