It can take a while before all air has disappeared from a filled installation.

Especially in the first week noises may be heard which indicate the presence

of air. The automatic air vent in the boiler will remove the air, which means

the water pressure can reduce during this period and therefore topping off

with water will have to be done.

During normal use the following messages can occur with the necessary follow up:

NOTICE

i

Water pressure is too low (<14.5 PSI /
1.0 bar), flashing FILL will alternate with
indication of water pressure, boiler power
of 50% is possible. The installation needs
to be topped off.

Water pressure is too high (>52.2 PSI
/ 3.5 bar), if HIGH indication remains
continuously visible, the boiler is taken
out of operation. The installation pressure
needs to be decreased by draining water.

Water pressure is too low (<10 PSI / 0.7
bar), FILL indication remains continuously
visible, the boiler is taken out of operation.
The installation needs to be topped off.

10.3 Hot water supply

Apply the water pipe pressure to the tank (open main valve and/or stop valve of the
safety group).

Vent the tank and the hot water installation by opening a hot water shut off valve.
Leave the tap open for as long as required until all air has disappeared from the tank

and the pipes and only water is flowing from the shut off valve.