Installation & Servicing Instructions Rinnai Q-Series

34

The termination shall be at least 4 feet (1,220 mm) for the US and 6 feet (1,830

mm) for Canada distance from electric meters, gas meters, regulators and

relief equipment. (for room air application only)
Horizontal vent systems should always be installed sloping towards the

boiler (min. 21 mm/m, 1/4 “/ feet), in order to avoid condensate retaining in

the vent system. With the condensate running back to the boiler the risk of

ice forming at the terminal is reduced.
The whole route of the vent system must be installed upwards, never

downwards, completely nor partly.
Place pipe supports every 4 feet (1,219 mm) of horizontal run, beginning with

support near the boiler to prevent movement in fittings and allow boiler to be

free from any strain or weight on boiler or fittings.
The terminal should be located where dispersal of combustion products is

not impeded and with due regard for the damage or discolouration that might

occur to building products in the vicinity (see fig 16 and 17).

In certain weather conditions condensation may also accumulate on the

outside of the air inlet pipe. Such conditions must be considered and where

necessary insulation of the inlet pipe may be required.

In cold and/or humid weather water vapor may condense on leaving the vent

terminal. The effect of such ‘water condensation’ must be considered.
The terminal must be located in a place not likely to cause a nuisance.

Use the Instructions of the Rinnai venting system for installation and service.

Cellular or Foam core PVC is not permitted for use with the boiler.

NOTICE

i

!

CAUTION

!

CAUTION

NOTICE

i

NOTICE

i

NOTICE

i

NOTICE

i

Approval codes for installation of venting system

table 7

Item Description

Flue Material

United States

PVC Schedule 40

ANSI/ASTM D1785

PVC - DWV

ANSI/ASTM D2665

CPVC Schedule 40 ANSI/ASTM F441
PVC

ANSI/ASTM D2564

CPVC

ANSI/ASTM F493

Item Description

Flue Material

Manufacturer

Approval code
US/CAN

Flue system

Stainless steel vent
systems

Stainless Steel

Ubbink

Rolux Condensing
Vent System

Plastic Vent System

PPS

Ubbink

Rolux Condensing
Vent System

Plastic Vent System

PVC/CPVC

IPEX

ULC S636

System 636

Stainless steel vent
systems

Stainless Steel

Simpson Dura-Vent

FastNSeal Flex

UL1738 Flexible liner

Saf-T Vent SC
Saf-T Vent EZ Seal

Stainless steel vent
systems

Stainless Steel

Heat Fab

concentric

UL1738 twin pipe

Approval Codes for Installation

Canada

Plastic Vent and/or air
pipes and fittings

ULC S636

Plastic Pipe cement and
primer