Enviro 6G50 76N Manuel d'utilisation

Page 35

Advertising
background image

35

#

led status

proBleM

solutIon

7

8

9

Self diagnostic check has detected

a problem with the gas valve driver

circuit, internal microprocessor, or

other internal circuits.

1 Turn the power off for 10-20 seconds then on again to

clear these error codes.

2 If any of these error codes persist or cannot be cleared

- replace the gas control valve/thermostat.

10

The gas control valve/thermostat

has sensed main burner flame out

of proper sequence.

1 Turn the power off for 10-20 seconds then on again to

clear these error codes.

2 Replace the gas control valve/thermostat if this error

code persists.

11

Water temperature in the tank has

exceeded 195° F and has activated

the ECO (energy cut off) high

temperature limit.

1 Turn the power off for 10-20 seconds then on again to

clear these error codes.

2 Replace the gas control valve/thermostat if the error

code persists.

12

Self diagnostic check has detected

that one or both of the temperature

adjust buttons are stuck.

1 Press and release both temperature adjust buttons

several times - cycle water heater power off and on.

2 Replace the gas control valve/thermostat if the error

code persists.

13

Self diagnostic check has detected

the water temperature sensor

(located in the control valve's

immersion probe) is either open or

shorted.

1 Turn the power off for 10-20 seconds then on again to

clear these error codes.

2 Replace the gas control valve/thermostat if the error

code persists.

14

Self diagnostic check has detected

a problem with black resistor wire

on the ignitor assembly plug;

resistor wire is open or shorted.

1 Turn off power to the water heater. Ensure black

resistor wire is not cut, missing, and is installed

between pins 3 & 4 of ignitor assembly plug. Replace

ignitor assembly if damaged or defective.

2 Replace the gas control valve/thermostat if the error

code persists.

15

Self diagnostic check has

determined resistance of the black

resistor wire on ignitor assembly

plug is not within tolerance.

1 Turn off power to the water heater.

2 Replace the igniter assembly plug.

3 Replace the gas control valve/thermostat if the error

code persists.

16

The gas control valve/thermostat

has detected the air pressure switch

circuit is opening repeatedly during

one heating cycle.

1 Ensure air pressure switch hose is not kinked or

clogged, ensure the blower housing is clear of any

condensation.

2 Check vent temperature limit switch - if it is determined

that the vent temperature limit switch is opening its

contacts at normal operating temperatures during

heating cycle - replace the vent temperature limit

switch.

3 Ensure water heater is not over-firing. Call the technical

support for further assistance.