24

vent attenuatIon asseMBlY

InstallatIon InstructIons

The Vent Attenuation Assembly (VAA) is designed to provide a

reduction in fan noise created in the blower wheel. This installation

of this VAA is optional. Review directions thoroughly prior to installing

the new VAA. Please contact the manufacturer of the water heater as

shown in the instruction manual with any questions or for additional

product support.

vent attenuatIon asseMBlY KIt parts lIst

The kit consists of the following items. If a part is missing, use the

contact information in the instruction manual to acquire missing

component(s).

• vent attenuation assembly

• flexible tubing

• hose barb

• hex plug (installed on VAA)

• instruction sheet

vent attenuatIon asseMBlY InstallatIon

The VAA is designed for both vertical and horizontal installations.

The vertical installation does not require the additional hose barb

and flexible tubing. However, the horizontal installation will require

the hose barb and flexible tubing to release condensate buildup

from the VAA. See instructions and diagrams that follow for a more

detailed description.

Breathing Hazard - Carbon Monoxide Gas

Do NOT block the holes in the hex plug of vent pipe

assembly #1.

Do NOT elevate any portion of the field supplied drain

line beyond the 1/2" adaptor above the adaptor. This

must be true for entire length of the drain line including

the exit into an appropriate drain.

Condensate lines must be free and clear of debris and

must not allow back flow through drain line. Condensate

lines must be able to flow freely to an appropriate drain.

Do not allow condensate lines to become crimped closed.

Analyze entire vent system to make sure that condensate

will not become trapped in a section of vent pipe and

therefore reduce open cross sectional area of vent.

Breathing carbon monoxide can cause brain damage or death.

Always read and understand instruction manual.

Vertical VAA Installations (Recommended)
1. The VAA is designed to accept two inch PVC pipe into

the adapters on both ends. The VAA can be installed to the

piping from either side (there is no specific inlet or outlet). For

optimum performance, install VAA as close as possible to

the blower assembly.

2. Following the vent pipe manufacturer ’s instruction, glue the

two inch PVC pipe coming from the blower into the VAA.

3. Perform the same sequence on the PVC pipe coming from the

exhaust side (vent terminal side) of the VAA.

4. Make sure the VAA and vent pipe is supported securely to a

permanent fixture (stud or wall). Use standard support straps (not

supplied with kit) that may be found at a local hardware store.

Failure to properly support the VAA and the surrounding vent

pipe could create a hazardous situation. DO NOT puncture any

surface of the VAA.

5. Confirm that the hex plug is securely installed in the 1/2” fitting

found on the center of the VAA pipe. It is imperative that the plug

is secure and air tight to prevent any combustion gases escaping

into the room. If the plug is not securely tightened, remove and

reinstall using Teflon tape on the threads. Since neither hose

barb nor flexible tubing is used on the VAA, any unused open

barb fittings on vent pipe assembly #2 need to be plugged using

break-away plugs. Once installed along with the rest of the vent

configuration, make sure to operate the unit through at least one

heat up cycle to ensure there is no leakage around the plug or

any joints of the VAA or vent pipe system.

fIGure 22: typical vertical Installation

horizontal vaa Installations
1. The VAA is designed to accept two inch PVC pipe into the

adapters on both ends. The VAA can be installed to the

piping from either side (there is no specific inlet or outlet). For

optimum performance, install VAA as close as possible to the

blower assembly.

2. Following the vent pipe manufacturer’s instruction, glue the

two inch PVC pipe coming from the blower into the VAA. Make

sure the 1/2” fitting is on the bottom side of the VAA. This will

be used to run the condensate hose to a suitable drain. See

typical vent installation in Figure 23.

3. Perform the same sequence on the PVC pipe coming from

the exhaust side (vent terminal side) of the VAA.

4. Make sure the VAA and vent pipe is supported securely to

a permanent fixture (stud or wall). Use standard support

straps (not supplied with kit) that may be found at a local

hardware store. Failure to properly support the VAA and the

surrounding vent pipe could create a hazardous situation. DO

NOT puncture any surface of the VAA.

5. Remove hex plug from the center pipe of the VAA. Locate

the hose barb and install into the 1/2” fitting on the center of

the VAA. Using Teflon tape on the threads, install hose barb

into 1/2” fitting securely. It is imperative that the hose barb is

secure and tight to prevent any combustion gases escaping

into the room.

6. Locate flexible tubing. Slide one end of tube over the hose barb

located on the center pipe of the VAA. The ridges on the hose barb

should prevent the tube from sliding off, however, to ensure there

are no leaks and possible dislocation from hose barb, use a wire

tie or hose clamp (not supplied with kit) and secure.