Figure 7. The water heater should have clearances of at least 1 inch

(25 mm) from the sides and back and 6 inches (150 mm) from the front

of the appliance. The opening should directly communicate with the

outdoors or should communicate through a vertical or horizontal duct

to the outdoors or spaces that freely communicate with the outdoors

and should have a minimum free area of the following:
1. 1 square inch per 3000 Btu/hr (700 mm

2

per kW) of the total input

rating of all appliances located in the enclosure, and

2. Not less than the sum of the areas of all vent connectors in space.

outdoor aIr throuGh two horIZontal ducts

fIGure 8.

Confined space should be provided with two permanent horizontal

ducts, one commencing within 12 inches (300 mm) of top and one

commencing within 12 inches (300 mm) of bottom of enclosure. Horizontal

ducts should communicate directly with outdoors. See Figure 8.
Each duct opening should have a minimum free area of 1 square inch

per 2,000 Btu/hr (1100 mm

2

per kW) of the aggregate input rating of all

appliances installed in the enclosure.
When ducts are used, they should be of the same cross sectional area

as the free area of the openings to which they connect. The minimum

dimension of rectangular air ducts should be not less than 3 inches.

outdoor aIr throuGh two vertIcal ducts

The illustrations shown in this section of the manual are a reference for

the openings that provide fresh air into confined spaces only.
Do not refer to these illustrations for the purpose of vent installation.

See Installation of Vent System on pages 19-20 for complete venting

installation instructions.

fIGure 9.

The confined space should be provided with two permanent vertical

ducts, one commencing within 12 inches (300 mm) of the top and

one commencing within 12 inches (300 mm) of the bottom of the

enclosure. The vertical ducts should communicate directly with the

outdoors. See Figure 9.

Each duct opening should have a minimum free area of 1 square inch

per 4,000 Btu/hr (550 mm

2

per kW) of the aggregate input rating of

all appliances installed in the enclosure.

When ducts are used, they should be of the same cross sectional

area as the free area of the openings to which they connect. The

minimum dimension of rectangular air ducts should be not less than

3 inches.

aIr froM other Indoor spaces

fIGure 9a.

The confined space should be provided with two permanent

openings, one commencing within 12 inches (300 mm) of the top

and one commencing within 12 inches (300 mm) of the bottom of

the enclosure. See Figure 9A.

Each opening should communicate directly with an additional room(s)

of sufficient volume so that the combined volume of all spaces meets

the criteria for an Unconfined Space.

Each opening should have a minimum free area of 1 square inch per

1,000 Btu/hr (1100 mm

2

per kW) of the aggregate input rating of all

appliances installed in the enclosure. Each opening should not be

less than 100 square inches (645 cm

2

).