Enviro 6G50 76N Manuel d'utilisation

Page 12

Advertising
background image

12

Such a condition often will result in a yellow, luminous burner

flame, causing sooting of the combustion chamber, burners and

flue tubes and creates a risk of asphyxiation.

Do not install the water heater in a confined space unless an

adequate supply of air for combustion and ventilation is brought in

to that space using the methods described in the Confined Space

section that follows.
Never obstruct the flow of ventilation air. If you have any doubts or

questions at all, call your gas supplier. Failure to provide the proper

amount of combustion air can result in a fire or explosion and cause

property damage, serious bodily injury or death.

unconfIned space

An Unconfined Space is one whose volume is not less than 50 cubic

feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input

rating of all appliances installed in the space. Rooms communicating

directly with the space, in which the appliances are installed, through

openings not furnished with doors, are considered a part of the

unconfined space.

Makeup air requirements for the operation of exhaust fans, kitchen

ventilation systems, clothes dryers and fireplaces should also be

considered in determining the adequacy of a space to provide

combustion, ventilation and dilution air.

unusuallY tIGht constructIon

In unconfined spaces in buildings, infiltration may be adequate to

provide air for combustion, ventilation and dilution of flue gases.

However, in buildings of unusually tight construction (for example,

weather stripping, heavily insulated, caulked, vapor barrier, etc.)

additional air must be provided using the methods described in the

Confined Space section that follows.

confIned space

A Confined Space is one whose volume is less than 50 cubic feet

per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input rating

of all appliances installed in the space.

Openings must be installed to provide fresh air for combustion,

ventilation and dilution in confined spaces. The required size for the

openings is dependent on the method used to provide fresh air to

the confined space and the total Btu/hr input rating of all appliances

installed in the space.

dIrect vent applIances

Appliances installed in a Direct Vent configuration that derive all

air for combustion from the outdoor atmosphere through sealed

intake air piping are not factored in the total appliance input Btu/hr

calculations used to determine the size of openings providing fresh

air into confined spaces.

EXHAUST FANS

Where exhaust fans are installed, additional air should be provided

to replace the exhausted air. When an exhaust fan is installed in

the same space with a water heater, sufficient openings to provide

fresh air must be provided that accommodate the requirements for

all appliances in the room and the exhaust fan. Undersized openings

will cause air to be drawn into the room through the water heater’s

vent system causing poor combustion. Sooting, serious damage to

the water heater and the risk of fire or explosion may result. It can

also create a risk of asphyxiation.

louvers and GrIlles

The free areas of fresh air openings in instructions that follow do not take

in to account presence of louvers, grilles or screens in openings.
The required size of openings for combustion, ventilation and dilution

air should be based on the “net free area” of each opening. Where

the free area through a design of louver or grille or screen is known, it

should be used in calculating the size of opening required to provide the

free area specified. Where the louver and grille design and free area

are not known, it should be assumed that wood louvers will have 25%

free area and metal louvers and grilles will have 75% free area. Non

motorized louvers and grilles should be fixed in the open position.

fresh aIr openInGs for confIned spaces

The following instructions should be used to calculate the size,

number and placement of openings providing fresh air for combustion,

ventilation and dilution in confined spaces. The illustrations shown in

this section of the manual are a reference for the openings that provide

fresh air into confined spaces only. Do not refer to these illustrations

for the purpose of vent installation. See Installation of Vent System on

pages 18-25 for complete venting installation instructions.

outdoor aIr throuGh two openInGs

fIGure 6.

The confined space should be provided with two permanent

openings, one commencing within 12 inches (300 mm) of the top

and one commencing within 12 inches (300 mm) of the bottom of

the enclosure. The openings should communicate directly with

the outdoors. See Figure 6.
Each opening should have a minimum free area of 1 square inch

per 4,000 Btu/hr (550 mm

2

per kW) of the aggregate input rating

of all appliances installed in the enclosure. Each opening should

not be less than 100 square inches (645 cm

2

).

outdoor aIr throuGh one openInG

fIGure 7.

Alternatively a single permanent opening, commencing within 12

inches (300 mm) of the top of the enclosure, should be provided. See

Advertising