Caution, Danger – Enviro 6G50 76N Manuel d'utilisation

Page 16

Advertising
background image

16

exceed the marked hydrostatic working pressure of the water heater

(150 psi = 1,035 kPa) and a discharge capacity not less than the

water heater Btu/hr or kW input rate as shown on the water heater’s

model rating plate.

Note: In addition to the factory installed Temperature-Pressure

Relief Valve on the water heater, each remote storage tank that

may be installed and piped to a water heating appliance must also

have its own properly sized, rated and approved Temperature-

Pressure Relief Valve installed. Call the toll free technical support

phone number listed on the back cover of this manual for technical

assistance in sizing a Temperature-Pressure Relief Valve for remote

storage tanks.

For safe operation of the water heater, the Temperature-Pressure

Relief Valve must not be removed from its designated opening

nor plugged. The Temperature-Pressure Relief Valve must be

installed directly into the fitting of the water heater designed for the

relief valve. Install discharge piping so that any discharge will exit

the pipe within 6 inches (15.2 cm) above an adequate floor drain,

or external to the building. In cold climates it is recommended

that it be terminated at an adequate drain inside the building. Be

certain that no contact is made with any live electrical part. The

discharge opening must not be blocked or reduced in size under

any circumstances. Excessive length, over 30 feet (9.14 m), or use

of more than four elbows can cause restriction and reduce the

discharge capacity of the valve.

No valve or other obstruction is to be placed between the

Temperature-Pressure Relief Valve and the tank. Do not connect

discharge piping directly to the drain unless a 6” (15.2 cm) air gap

is provided. To prevent bodily injury, hazard to life, or property

damage, the relief valve must be allowed to discharge water in

adequate quantities should circumstances demand. If the discharge

pipe is not connected to a drain or other suitable means, the water

flow may cause property damage.

CAUTION

Temperature-Pressure Relief Valve discharge

pipe must terminate at adequate drain.

Water Damage Hazard

t&p valve discharge pipe requirements:
• Should not be smaller in size than the outlet pipe size of the valve, or

have any reducing couplings or other restrictions.

• Should not be plugged or blocked.

• Should not be exposed to freezing temperatures.

• Should be of material listed for hot water distribution.

• Should be installed so as to allow complete drainage of both the

Temperature-Pressure Relief Valve and the discharge pipe.

• Must terminate a maximum of six inches above a floor drain or external

to the building. In cold climates, it is recommended that the discharge

pipe be terminated at an adequate drain inside the building.

• Should not have any valve or other obstruction between the relief

valve and the drain.

DANGER

Burn hazard.

Hot water discharge.

Keep clear of Temperature-

Pressure Relief Valve

discharge outlet.

The Temperature-Pressure Relief Valve must be manually

operated at least twice a year. Caution should be taken to ensure

that (1) no one is in front of or around the outlet of the Temperature-

Pressure Relief Valve discharge line, and (2) the water manually

discharged will not cause any bodily injury or property damage

because the water may be extremely hot. If after manually

operating the valve, it fails to completely reset and continues

to release water, immediately close the cold water inlet to the

water heater, follow the draining instructions in this manual, and

replace the Temperature-Pressure Relief Valve with a properly

rated/sized new one.

note: The purpose of a Temperature-Pressure Relief Valve is to

prevent excessive temperatures and pressures in the storage tank.

The T&P valve is not intended for the constant relief of thermal

expansion. A properly sized thermal expansion tank must be

installed on all closed systems to control thermal expansion, see

Closed Water Systems and Thermal Expansion on page 14-15.

If you do not understand these instructions or have any questions

regarding the Temperature-Pressure Relief Valve call the toll

free number listed on the back cover of this manual for technical

assistance.

hIGh altItude InstallatIon

This heater is approved for operation up to 5,300 feet (1,615 m)

without alteration. High altitude models are available from the

factory for elevations between 5,300 feet (1,615 m) and 10,100

feet (3,079 m). For elevations above 10,100 feet (3,079 m) the

input rating should be reduced at the rate of 4 percent for each

1,000 feet (305 m) above sea level which requires replacement

of the burner orifice. Contact your local gas supplier for further

information.

Advertising