Enviro 6G50 76N Manuel d'utilisation

Page 20

Advertising
background image

20

plannInG the vent sYsteM

Plan the route of the vent system from the discharge of the blower

to the planned location of the vent terminal. Refer to VAA instruction

on page 24 while planning the vent system.

1. Layout total vent system to use a minimum of vent pipe and elbows.
2. This water heater is capable of venting flue gases equivalent

to 25’ (7.6 m) of 2” pipe, 65’ (19.8 m) of 3” pipe, or 128’ (39.0 m)

of 4” pipe as listed in Table 1.

taBle 1

Number of 2” Maximum 3” Maximum 4” Maximum

90° Elbows Pipe - ft. (m)

Pipe - ft. (m)

Pipe - ft. (m)

1

20 (6.1)

60 (18.3)

120 (36.6)

2

15 (4.6)

55 (16.8)

112 (34.1)

3

10 (3.0)

50 (15.2)

104 (31.7)

4

--

45 (13.7)

96 (29.3)

5

--

40 (12.2)

88 (26.8)

6

--

35 (10.7)

80 (24.3)

The minimum vent lengths for each of the pipe sizes is one 90° on top of

the unit plus 2’ (61cm) of straight pipe and the appropriate termination.

note: The equivalent feet (m) of pipe listed above are exclusive

of the termination. That is, the termination, with an installed

screen, is assumed to be in the system and the remainder of the

system must not exceed the lengths discussed above.

3. The blower discharge adapter is made to accept only straight

sections of 2” pipe. To start, a minimum of 2 inches (5.1 cm) of

2” pipe must be attached to the blower discharge, see Figure 17.

If using 2” inch vent pipe:

A minimum of 2 inches (5.1 cm) must be attached to the blower

before the first elbow. After the first elbow add the additional

venting required for the installation. The total system cannot

exceed the lengths discussed above, where each elbow is equal

to 5 feet (1.5 m) of straight pipe.

If using 3” or 4” inch vent pipe:

Two inches (5.1 cm) of pipe must be attached to blower

discharge before adding a reducer to acquire desired pipe

diameter. An appropriately sized 45 degree schedule 40 DWV

elbow (field supplied) vent terminal must be obtained with

an equivalent screen (supplied in vent kit). The total system

cannot exceed equivalent pipe lengths discussed above

where each elbow is equal to 5 feet (1.5 m) of straight pipe

(3” vent pipe) or 8 feet (2.4 m) of straight pipe (4” vent pipe).

Installation of this water heater must comply with CAN/CSA B149.1 -

Natural Gas and Propane Installation Code which requires the vent

system components be certified to ULC S636.

This water heater has been design certified to be vented with PVC

or CPVC pipe certified and marked as complying with ULC S636.

This water heater is supplied with a 2 inch 22.5 degree termination

elbow. Any outlet piping, fittings and glue used to vent this appliance

that is not supplied by the manufacturer must comply with the ULC

S636 requirements.

If water heater is being installed as a replacement for an existing

power vented heater in pre-existing venting, a thorough inspection

of existing venting system must be performed prior to any installation

work. Verify that correct material as detailed above has been used,

and that minimum or maximum vent lengths and terminal location

as detailed in this manual have been met. Carefully inspect entire

venting system for any signs of cracks or fractures, particularly at

joints between elbows and other fittings and straight runs of vent

pipe. Check system for signs of sagging or other stresses in joints

as a result of misalignment of any components in system. If any of

these conditions are found, they must be corrected in accordance

with venting instructions in this manual before completing installation

and putting water heater into service.

note: a. For water heaters in locations with high ambient

temperatures above 100°F (38°C) it is recommended that CPVC

pipe and fittings be used.

B. A 22.5 degree elbow (2” vent pipe) or

a 45 degree elbow (3” and 4” vent pipe) with an installed screen

VENT TERMINAL must be used in all cases.

4. There will be some installations where condensate will be formed

in the horizontal runs of the vent system. This condensate will

run into the condensate boot attached to the blower and out the

fitting. The water heater is shipped with condensate hose that

attaches to the fitting on the condensate boot. No other Tee or

fitting is required. See Figures 17, 20 and 21.

condensate

This water heater is a condensing unit and requires a drain to be

located in close proximity to allow condensate to drain safely.

One hose from blower housing, two flexible hoses from blower

outlet adaptor, along with another flexible hose from VAA if

installed, run to barb fittings on vent pipe assembly #2. Hose

is clamped by rubber clips and flexible hoses by a clamp on

jacket top cover. See Figure 17. Condensate drains from the unit

at the exhaust tee located at the bottom of the unit (see figure

16). Condensate from this water heater is mildly acidic. Please

note that some local codes require that condensate is treated

by using a pH neutralizing filter prior to disposal.

NOTE: It is important that the field supplied drain lines beyond

the 1/2” adaptor of vent pipe assembly #1 should be installed

continuously tilted downward toward an appropriate drain. See

Figure 16. If these instructions are not followed or if condensate

drain line is blocked, water will spill from condensate trap. Do not

block the holes in the hex plug on top of a small tee in vent pipe

assembly #1. As with every water heater installation, a drain pan

should be used to prevent water damage to surrounding area. If

necessary, a condensate pump with an incorporated reservoir

may be used to pump water to an appropriate drain. To avoid

condensate spillage, select a pump with an overflow switch.

Caution must be used to ensure that drain is free and clear

of debris and will not allow backflow through the condensate

drain line. Consideration must be given to avoid freezing of

the condensate lines which could result in excessive build

up of condensate inside the water heater. Waterproof heat

tape may be required to prevent freezing of condensate lines.

Please ensure that the outlet of condensate drain does not

create a slippery condition which could lead to personal injury.

Care should be taken to ensure there is no kink or twist in any

condensate hose. If a VAA is not installed, the unused barb

fitting in vent pipe assembly #2 should be plugged using one

of the break-away plugs.

Breathing Hazard - Carbon Monoxide Gas

Do NOT block the holes in the hex plug of vent pipe

assembly #1.

Do NOT elevate any portion of the field supplied drain

line beyond the 1/2" adaptor above the adaptor. This

must be true for entire length of the drain line including

the exit into an appropriate drain.

Condensate lines must be free and clear of debris and

must not allow back flow through drain line. Condensate

lines must be able to flow freely to an appropriate drain.

Do not allow condensate lines to become crimped closed.

Analyze entire vent system to make sure that condensate

will not become trapped in a section of vent pipe and

therefore reduce open cross sectional area of vent.

Breathing carbon monoxide can cause brain damage or death.

Always read and understand instruction manual.

Advertising