Enviro 6G50 76N Manuel d'utilisation

Page 17

Advertising
background image

17

Failure to replace standard orifice with a high altitude orifice when

installed above 10,100 feet (3,079 m) could result in improper and

inefficient operation of the appliance, producing carbon monoxide

gas in excess of safe limits, which could result in serious injury or

death. Contact your gas supplier for any specific changes which

may be required in your area.

Gas pIpInG

Fire and Explosion Hazard

Do not use water heater with any

gas other than the gas shown on

the rating plate.

Excessive pressure to gas control

valve can cause serious injury or death
Turn off gas lines during installation.

Contact qualified installer or

service agency.

Make sure the gas supplied is the same type listed on the model

rating plate. The inlet gas pressure must not exceed 14 inch water

column (3.5 kPa) for natural and propane gas (L.P.). The minimum

inlet gas pressure shown on the rating plate is that which will

permit firing at rated input.

All gas piping must comply with local codes and ordinances or

with the Natural Gas and Propane Installation Code (CAN/CSA

B149.1). Copper or brass tubing and fittings (except tin lined copper

tubing) should not be used.

If the gas control valve is subjected to pressures exceeding 1/2

psi (3.5 kPa), the damage to the gas control valve could result in

a fire or explosion from leaking gas.

If the main gas line Shut-off serving all gas appliances is used,

also turn “off” the gas at each appliance. Leave all gas appliances

shut “off” until the water heater installation is complete.

A gas line of sufficient size must be run to the water heater. Consult

the current edition of the Natural Gas and Propane Installation

Code (CAN/CSA B149.1) and your gas supplier concerning pipe

size.

There must be:

• A readily accessible manual shut off valve in the gas supply line

serving the water heater, and

• A drip leg (sediment trap) ahead of gas control valve to help

prevent dirt and foreign materials from entering the gas control

valve.

• A flexible gas connector or a ground joint union between the

shut off valve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting the

water heater. Use a soapy water solution, not a match or open

flame. Rinse off soapy solution and wipe dry.

Use pipe joint compound or teflon tape marked as being resistant

to the action of petroleum [Propane (L.P.)] gases.

The appliance and its gas connection must be leak tested before

placing the appliance in operation.

The appliance and its individual Shut-off valve should be

disconnected from the gas supply piping system during any

pressure testing of that system at test pressures in excess of 1/2

pound per square inch (3.5 kPa). It should be isolated from the gas

supply piping system by closing its individual manual Shut-off valve

during any pressure testing of the gas supply piping system at test

pressures equal to or less than 1/2 pound per square inch (3.5 kPa).

Connecting gas piping to the gas control valve of water heater can be

accomplished by either of two methods shown in Figures 12 and 13.

fIGure 12. Gas pIpInG wIth

FLEXIBLE CONNECTOR.

fIGure 13. Gas pIpInG wIth all

BlacK Iron pIpe to Gas control.

Advertising